CHARACTERISTICS
Two AC inputs with integrated transfer switch
Two AC outputs
The main output has no-break functionality. The second output is live only when AC is available on
one of the inputs of the Quattro.
Virtually unlimited power thanks to parallel operation
Up to 6 Quattro’s can operate in parallel.
Three phase capability
Three units can be con gured for three-phase output.
PowerControl - Dealing with limited generator, shore-side or grid power
PowerAssist - Boosting shore or generator power
Solar energy: AC power available even during a grid failure
The Quattro can be used in o grid as well as grid connected PV and other alternative
energy systems.
• A grid connected PV system will shit down when the grid fails! Not anymore with a
Quattro and batteries
[ 24V: 3000 VA ]
[ 24V: 5000 VA ]
[ 48V: 5000 VA ]
QUATTRO 5KVA
230VAC/50HZ
Quattro 24/3000/70 24/5000/120 48/5000/70
PowerControl / PowerAssist Yes Yes Yes
Integrated Transfer switch Yes Yes Yes
AC inputs (2x) Input voltage range: 187-265 VAC Input frequency: 45-55 Hz Power factor: 1
Maximum feed through current (A) 50 30 30
INVERTER
Input voltage range (V DC) 19-33 19-33 38-66
Output (1) Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0.1 %
Cont. output power at 25 ˚C (VA) (2) 3000 5000 5000
Cont. output power at 25 ˚C (W) 2500 4250 4250
Cont. output power at 40 ˚C (W) 2000 3350 3350
Peak power (W) 6000 7500 7800
Maximum e ciency (%) 94 94 95
Zero-load power (W) 15 30 30
Load shedding output 25 10 Switches o when no external AC source available
CHARGER
Charge voltage ‘absorption’ (V DC) 28.8 28.8 57.6
Charge voltage ‘ oat (V DC) 27.6 27.6 55.2
Storage mode (V DC) 26.4 26.4 52.8
Charge current house battery (A) 70 120 70
Charge current starter battery (A) 4
Battery temperature sensor Yes Yes Yes
GENERAL
Multi purpose relay (1) Yes Yes Yes
Protection (3) a-f
Common Characteristics Operating temp.: -20 to +50 ˚C (fan assisted cooling) Humidity (non condensing) : max 95%
ENCLOSURE
Common Characteristics Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Battery-connection Four M8 bolts (2 plus and 2 minus connections)
230 V AC-connection Screw clamp 13 mm² (AWG 6)
Weight (kg) 30
Dimensions (hxwxd in mm) 362x258x218 444x328x240
STANDARDS
Safety EN 60335-1, EN 60335-2-29
Emissions / immunity EN 55014-1, EN 61000-3-2 / EN 55014-2, EN61000-3-3
Automotive Directive 2004/104/EC
1) Multipurpose relay which can be set for general alarm, DC undervoltage or genset starts signal function
2) Suitable for parallel and 3-phase 3) Protection
a. Output short circuit b. Overload c. Battery voltage too high
d. Battery voltage too low e. Battery reverse polarity detection f. 230 V AC on inverter output
g. Input voltage riplle too high h. Temperature too high