Victron energy 24/30 Spezifikationen Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 20
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
PHOENIX MULTIPLUS
230VAC/50HZ
CHARACTERISTICS
Multi-functional, with intelligent mains and generator power management
The multi gets its name from the multiple functions it can perform. It is a powerful true sine wave inverter, a sophisticated
battery charger that features adaptive charge technology, and a high-speed AC transfer switch in a single compact
enclosure.
Uninterrupted AC power (UPS function)
In the event of a grid failure, or mains or generator power being disconnected, the inverter within the Multi is automatically
activated and takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that
computers and other electronic equipment will continue to operate without disruption.
PowerControl - Dealing with limited generator, shore side or grid power
With the Phoenix Multi Control Panel a maximum generator or shore current can be set. The Multi will then take account of
other AC loads and use whatever is extra for charging, this preventing the generator or mains supply from being
overloaded.
PowerAssist - Boosting the capacity of grid or generator power, an innovative feature of the MultiPlus
This feature takes the principle of PowerControl to a further dimension allowing the MultiPlus to supplement the capacity
of the alternative source. Where peak power is so often required only for a limited period, the Phoenix MultiPlus will make
sure that insu cient shore or generator power is immediately compensated for by power from the battery.
Four stage adaptive charger and dual bank battery charging
The main output provides a powerful charge to the battery system by means of advanced ‘adaptive charge’ software that
ne-tunes the three stage automatic process to suit the condition of the battery, and adds a fourth stage for long periods
of oat charging. In addition to this, the Multi will charge a second battery using an independent trickle charge output
intended for a main engine or generator starter battery.
[ 12V: 800-3000 VA ]
[ 24V: 800-3000 VA ]
[ 48V: 3000 VA ]
ACCESSORIES
Multiplus 12V / 24V / 48V C12/800/35
C24/800/16
C12/1200/50
C24/1200/25
C12/1600/70
C24/1600/40
C12/2000/80
C24/2000/50
12/3000/120
24/3000/70
48/3000/35
PowerControl Yes
PowerAssist - Yes (Multiplus) Yes
Transfer switch (A) 16 16 16 30 16 or 50
INVERTER
Input voltage range (VCD) 9.5-17V 19-33V 38-66V
Output 230 V ± 2% /50 Hz ± 0,1%
Cont. output power at 25 ˚C (VA) (5) 800 1200 1600 2000 3000 (4)
Cont. output power at 25/40 ˚C (W) 700/650 1000/900 1300/1200 1600/1450 2500/2000
Peak power (W) 1600 2400 3000 4000 6000
Maximum e ciency (%) 92/94 93/94 93/94 93/94 93/94/95
Zero-load power (W) 5/8 5/8 5/8 10/10 10/10/12
CHARGER
AC input 187-265 VAC, 45-55 HZ, Power factor:1
Charge voltage ‘absorption’ (V DC) 14.4 / 28.8 / 57.6
Charge voltage ‘ oat’ (V DC) 13.8 / 27.6 / 55.2
Storage mode (V DC) 13.2 / 26.4 / 52.8
Charge current house battery (A)(4) 35 / 16 50 / 25 70 / 40 80 / 50 120 / 70 / 40
Charge current starter battery (A) 4
Battery temperature sensor Yes
GENERAL
Multi purpose relay driver or relay Relay driver (2) Relay (3)
Protection (5) a,b,c,d,f,g,h a-h
Common Characteristics Operating temp. range: -20 - 50 ˚C (fan assisted cooling)
Humidity (non condesing) : max 95%
ENCLOSURE
Common Characteristics Material & Colour: aluminum (blue RAL 5012)
Battery-connection (1) M8 Studs
230 V AC-connection G-ST 18i Spring-clamp Scre-clamp
Protection category IP 21
Weight (kg) 10 10 10 12 18
Dimensions (hxwxd in mm) 375x214x110 520x255x125 362x258x218
STANDARDS
Safety EN 60335-1, EN60335-2-29
Emission / Immunity EN 55014-1, EN 55014-2 / EN 61000-3-2, EN 61000-3-3
Automotive Directive 95/94/EC and 2004/104/EC
1) Battery cables of 1.5 meter 2) Relay driver: open Collector 66V
3) Multipurpose relay which can be set for general alarm, DC undervoltage or genset starts signal function
4) Suitable for parallel and 3-phase 5) Protection
a. Output short circuit b. Overload c. Battery voltage too high
d. Battery voltage too low e. Battery reverse polarity detection f. 230 V AC on inverter output
g. Input voltage riplle too high h. Temperature too high
VVC: VE.Net to VE BUS
Converter
Victron Global Remote
Phoenix Multi Control
This is a remote control
and monitoring panel
for the Phoenix Multiplus
Seitenansicht 4